Template zabbix RITTAL CMC II SNMP

<?xml version="1.0" encoding="UTF-8"?>
<zabbix_export>
    <version>3.2</version>
    <date>2020-04-01T20:15:30Z</date>
    <groups>
        <group>
            <name>SALA COFRE</name>
        </group>
    </groups>
    <hosts>
        <host>
            <host>SALA-COFRE</host>
            <name>SALA-COFRE</name>
            <description>CMC - Monitoramento da Sala Cofre</description>
            <proxy/>
            <status>1</status>
            <ipmi_authtype>-1</ipmi_authtype>
            <ipmi_privilege>2</ipmi_privilege>
            <ipmi_username/>
            <ipmi_password/>
            <tls_connect>1</tls_connect>
            <tls_accept>1</tls_accept>
            <tls_issuer/>
            <tls_subject/>
            <tls_psk_identity/>
            <tls_psk/>
            <templates>
                <template>
                    <name>Template ICMP Ping</name>
                </template>
            </templates>
            <groups>
                <group>
                    <name>SALA COFRE</name>
                </group>
            </groups>
            <interfaces>
                <interface>
                    <default>1</default>
                    <type>2</type>
                    <useip>1</useip>
                    <ip>192.168.12.85</ip>
                    <dns/>
                    <port>161</port>
                    <bulk>0</bulk>
                    <interface_ref>if1</interface_ref>
                </interface>
            </interfaces>
            <applications>
                <application>
                    <name>Alertas sala cofre</name>
                </application>
                <application>
                    <name>Sistema</name>
                </application>
            </applications>
            <items>
                <item>
                    <name>Uptime</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>1</multiplier>
                    <snmp_oid>iso.3.6.1.2.1.1.3.0</snmp_oid>
                    <key>cpu.cmc.tc.system.uptime</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units>uptime</units>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>0.01</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>0</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port/>
                    <description/>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Sistema</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Umidade Entrada Sala Cofre</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.3.5.2.1.5.2</snmp_oid>
                    <key>cpu.cmc.tc.unit1.sensor1.UmidadeEntradaSala</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units>%rH</units>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>0</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description>Umidade fundo Sala de Nobreaks</description>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Umidade Fundo Sala Cofre</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.3.5.2.1.5.4</snmp_oid>
                    <key>cpu.cmc.tc.unit1.sensor1.UmidadeFundoSala</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units>%rH</units>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>0</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description>Umidade fundo Sala de Nobreaks</description>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Temperatura Entrada Sala Cofre</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.3.5.2.1.5.1</snmp_oid>
                    <key>cpu.cmc.tc.unit1.sensorTempEntrada</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units>ºC</units>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>0</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description>Temperatura de Fundo da Sala Cofre</description>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Temperatura Fundo Sala Cofre</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.3.5.2.1.5.3</snmp_oid>
                    <key>cpu.cmc.tc.unit1.sensorTempFundo</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units>ºC</units>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>0</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description>Temperatura de Fundo da Sala Cofre</description>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>STATUS PORTA</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.4.5.2.1.5.4</snmp_oid>
                    <key>cpu.cmc.tc.unit2.sensor2</key>
                    <delay>5</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units/>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>3</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description/>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Ar-Condicionado Sala Cofre</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.4.5.2.1.5.2</snmp_oid>
                    <key>cpu.cmc.tc.unit2.sensorClima</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units/>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>3</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description/>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Detecção de líquidos</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.4.5.2.1.5.1</snmp_oid>
                    <key>cpu.cmc.tc.unit2.sensorDeteccaoLiquido</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units/>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>3</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description/>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Detecção de Fumaça</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>iso.3.6.1.4.1.2606.4.2.4.5.2.1.5.3</snmp_oid>
                    <key>cpu.cmc.tc.unit2.sensorFumaca</key>
                    <delay>120</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units/>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>3</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description/>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
                <item>
                    <name>Temperatura Sala Nobreaks</name>
                    <type>1</type>
                    <snmp_community>public</snmp_community>
                    <multiplier>0</multiplier>
                    <snmp_oid>1.3.6.1.4.1.2606.4.2.5.5.2.1.5.1</snmp_oid>
                    <key>cpu.cmc.tc.unit3.sensorTemp.nobreaks</key>
                    <delay>300</delay>
                    <history>90</history>
                    <trends>365</trends>
                    <status>0</status>
                    <value_type>3</value_type>
                    <allowed_hosts/>
                    <units>ºC</units>
                    <delta>0</delta>
                    <snmpv3_contextname/>
                    <snmpv3_securityname/>
                    <snmpv3_securitylevel>0</snmpv3_securitylevel>
                    <snmpv3_authprotocol>0</snmpv3_authprotocol>
                    <snmpv3_authpassphrase/>
                    <snmpv3_privprotocol>0</snmpv3_privprotocol>
                    <snmpv3_privpassphrase/>
                    <formula>1</formula>
                    <delay_flex/>
                    <params/>
                    <ipmi_sensor/>
                    <data_type>0</data_type>
                    <authtype>0</authtype>
                    <username/>
                    <password/>
                    <publickey/>
                    <privatekey/>
                    <port>161</port>
                    <description>Temperatura da Sala de Nobreaks</description>
                    <inventory_link>0</inventory_link>
                    <applications>
                        <application>
                            <name>Alertas sala cofre</name>
                        </application>
                    </applications>
                    <valuemap/>
                    <logtimefmt/>
                    <interface_ref>if1</interface_ref>
                </item>
            </items>
            <discovery_rules/>
            <httptests/>
            <macros/>
            <inventory/>
        </host>
    </hosts>
    <triggers>
        <trigger>
            <expression>{SALA-COFRE:cpu.cmc.tc.unit2.sensorDeteccaoLiquido.last()}=1</expression>
            <recovery_mode>0</recovery_mode>
            <recovery_expression/>
            <name>Atenção: Detecção de Líquido no piso</name>
            <correlation_mode>0</correlation_mode>
            <correlation_tag/>
            <url/>
            <status>0</status>
            <priority>4</priority>
            <description/>
            <type>0</type>
            <manual_close>0</manual_close>
            <dependencies/>
            <tags/>
        </trigger>
        <trigger>
            <expression>{SALA-COFRE:cpu.cmc.tc.unit2.sensorClima.last()}=1</expression>
            <recovery_mode>0</recovery_mode>
            <recovery_expression/>
            <name>Problema Ar-condicionado Sala Cofre</name>
            <correlation_mode>0</correlation_mode>
            <correlation_tag/>
            <url/>
            <status>0</status>
            <priority>4</priority>
            <description/>
            <type>0</type>
            <manual_close>0</manual_close>
            <dependencies/>
            <tags/>
        </trigger>
        <trigger>
            <expression>{SALA-COFRE:cpu.cmc.tc.unit2.sensor2.last()}=0</expression>
            <recovery_mode>0</recovery_mode>
            <recovery_expression/>
            <name>Status porta: Porta Aberta</name>
            <correlation_mode>0</correlation_mode>
            <correlation_tag/>
            <url/>
            <status>0</status>
            <priority>3</priority>
            <description/>
            <type>0</type>
            <manual_close>0</manual_close>
            <dependencies/>
            <tags/>
        </trigger>
        <trigger>
            <expression>{SALA-COFRE:cpu.cmc.tc.unit2.sensorFumaca.last()}=1</expression>
            <recovery_mode>0</recovery_mode>
            <recovery_expression/>
            <name>Urgencia: Alarme de Incendio Sala Cofre</name>
            <correlation_mode>0</correlation_mode>
            <correlation_tag/>
            <url/>
            <status>0</status>
            <priority>5</priority>
            <description/>
            <type>0</type>
            <manual_close>0</manual_close>
            <dependencies/>
            <tags/>
        </trigger>
    </triggers>
    <graphs>
        <graph>
            <name>Temperatura da Sala de Nobreaks</name>
            <width>900</width>
            <height>200</height>
            <yaxismin>0.0000</yaxismin>
            <yaxismax>100.0000</yaxismax>
            <show_work_period>1</show_work_period>
            <show_triggers>1</show_triggers>
            <type>0</type>
            <show_legend>1</show_legend>
            <show_3d>0</show_3d>
            <percent_left>0.0000</percent_left>
            <percent_right>0.0000</percent_right>
            <ymin_type_1>0</ymin_type_1>
            <ymax_type_1>0</ymax_type_1>
            <ymin_item_1>0</ymin_item_1>
            <ymax_item_1>0</ymax_item_1>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <drawtype>5</drawtype>
                    <color>EE0000</color>
                    <yaxisside>0</yaxisside>
                    <calc_fnc>2</calc_fnc>
                    <type>0</type>
                    <item>
                        <host>SALA-COFRE</host>
                        <key>cpu.cmc.tc.unit3.sensorTemp.nobreaks</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
        <graph>
            <name>Temperatura de Entrada Sala Cofre</name>
            <width>900</width>
            <height>200</height>
            <yaxismin>0.0000</yaxismin>
            <yaxismax>100.0000</yaxismax>
            <show_work_period>1</show_work_period>
            <show_triggers>1</show_triggers>
            <type>0</type>
            <show_legend>1</show_legend>
            <show_3d>0</show_3d>
            <percent_left>0.0000</percent_left>
            <percent_right>0.0000</percent_right>
            <ymin_type_1>0</ymin_type_1>
            <ymax_type_1>0</ymax_type_1>
            <ymin_item_1>0</ymin_item_1>
            <ymax_item_1>0</ymax_item_1>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <drawtype>5</drawtype>
                    <color>F63100</color>
                    <yaxisside>0</yaxisside>
                    <calc_fnc>2</calc_fnc>
                    <type>0</type>
                    <item>
                        <host>SALA-COFRE</host>
                        <key>cpu.cmc.tc.unit1.sensorTempEntrada</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
        <graph>
            <name>Temperatura de Fundo Sala Cofre</name>
            <width>900</width>
            <height>200</height>
            <yaxismin>0.0000</yaxismin>
            <yaxismax>100.0000</yaxismax>
            <show_work_period>1</show_work_period>
            <show_triggers>1</show_triggers>
            <type>0</type>
            <show_legend>1</show_legend>
            <show_3d>0</show_3d>
            <percent_left>0.0000</percent_left>
            <percent_right>0.0000</percent_right>
            <ymin_type_1>0</ymin_type_1>
            <ymax_type_1>0</ymax_type_1>
            <ymin_item_1>0</ymin_item_1>
            <ymax_item_1>0</ymax_item_1>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <drawtype>5</drawtype>
                    <color>F63100</color>
                    <yaxisside>0</yaxisside>
                    <calc_fnc>2</calc_fnc>
                    <type>0</type>
                    <item>
                        <host>SALA-COFRE</host>
                        <key>cpu.cmc.tc.unit1.sensorTempFundo</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
        <graph>
            <name>Umidade entrada Sala Cofre</name>
            <width>900</width>
            <height>200</height>
            <yaxismin>0.0000</yaxismin>
            <yaxismax>100.0000</yaxismax>
            <show_work_period>1</show_work_period>
            <show_triggers>1</show_triggers>
            <type>0</type>
            <show_legend>1</show_legend>
            <show_3d>0</show_3d>
            <percent_left>0.0000</percent_left>
            <percent_right>0.0000</percent_right>
            <ymin_type_1>0</ymin_type_1>
            <ymax_type_1>0</ymax_type_1>
            <ymin_item_1>0</ymin_item_1>
            <ymax_item_1>0</ymax_item_1>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <drawtype>5</drawtype>
                    <color>DD0000</color>
                    <yaxisside>0</yaxisside>
                    <calc_fnc>2</calc_fnc>
                    <type>0</type>
                    <item>
                        <host>SALA-COFRE</host>
                        <key>cpu.cmc.tc.unit1.sensor1.UmidadeFundoSala</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
        <graph>
            <name>Umidade fundo Sala Cofre</name>
            <width>900</width>
            <height>200</height>
            <yaxismin>0.0000</yaxismin>
            <yaxismax>100.0000</yaxismax>
            <show_work_period>1</show_work_period>
            <show_triggers>1</show_triggers>
            <type>0</type>
            <show_legend>1</show_legend>
            <show_3d>0</show_3d>
            <percent_left>0.0000</percent_left>
            <percent_right>0.0000</percent_right>
            <ymin_type_1>0</ymin_type_1>
            <ymax_type_1>0</ymax_type_1>
            <ymin_item_1>0</ymin_item_1>
            <ymax_item_1>0</ymax_item_1>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <drawtype>5</drawtype>
                    <color>F63100</color>
                    <yaxisside>0</yaxisside>
                    <calc_fnc>2</calc_fnc>
                    <type>0</type>
                    <item>
                        <host>SALA-COFRE</host>
                        <key>cpu.cmc.tc.unit1.sensor1.UmidadeFundoSala</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
    </graphs>
</zabbix_export>

Comentários